Lincoln High School ADA
Report
¨
Notes: All door hardware is not handicap
accessible.
Stair handrails in the original building do not
comply with handicap codes.
¨
At
the main entrance at connector, ramp leading to high school is too steep to not
have handrails.
¨
Boys’
bathroom next to classroom C2: Toilet is not handicap accessible. Urinal is not
handicap compliant. Accessories are not handicap accessible.
¨
Room
C1, which is a special needs room: Sink is not handicap accessible. Work
surfaces are not handicap accessible.
¨
Door
hardware for rooms C1, C2, C3, C4, C5 and C7 is not handicap accessible.
¨
Room
C6, Science Lab: Student stations and sinks are not handicap compliant. Fume hood is not handicap accessible.
Emergency shutoff button is not handicap accessible. Faculty demonstration desk
is not handicap accessible.
¨
C8,
Science Classroom: Emergency shutoff is not handicap accessible. The teacher’s
demonstration desk is not handicap accessible.
¨
C9,
Art Room: There is no side access to
the door.
¨
Last
two Science Labs: There is no side access to the entrance door.
¨
Men’s
Room across from cafeteria in new addition: The second vestibule door does not
have the required side clearance.
¨
C27
and C31: The exhaust fume is not handicap accessible.
¨
Prep
Room: Sink is not handicap accessible.
¨
Girls’
Room next to C2: Entrance vestibule door is not handicap accessible. It does
not have the required side clearance.
¨
Library/Media
Center: Entrance doors are not handicap compliant. They do not have the side
clearance or the correct door hardware. Circulation desk is not handicap
accessible.
¨
Auditorium:
There is no identified handicap seating area. There is no level area in back of
the auditorium in the intermediate seating or in the front of the auditorium.
There is no direct handicap access to the stage from the auditorium seating.
¨
222,
Art Room: There is no side clearance at the entrance. There are no handicap
accessible sinks.
¨
Music
Room: There are stairs leading to the music room from the corridor. This room
is not handicap accessible. There is no handicap door hardware and entrance to
the room does not have side clearance.
¨
Main
Office: Door hardware is not handicap accessible. The reception counter is not
handicap accessible.
¨
Bathroom
in office area: Entrance does not have side clearance. Sink and toilet are not
handicap accessible.
¨
223,
Home Ec.: The entrance door is not handicap accessible. It does not have the
hardware or the side clearance. Washer and dryer are not handicap accessible.
The work counter is not handicap accessible. In the food preparation area, the
stoves, refrigerators, and ovens are not handicap accessible.
¨
Men’s
Faculty Toilet Room next to room 223: There is no handicap accessible sink,
toilet, urinal or accessories. Door does not have side clearance.
¨
Women’s
Faculty Toilet Room: Door does not have side clearance. There is no handicap
accessible sink, toilet or accessories.
¨
222:
Door does not have the required side clearance.
¨
203,205,206,208:
No side clearance at the door.
¨
Room
205: Has raised platform that is not handicap accessible.
¨
Corridor
leading to gymnasium: The display cases protrude too far from the wall and are
mounted too high to prevent detection by a person with sight disabilities.
¨
218,
219, 220, 221: No side clearance at doors.
¨
216,
Science Lab: Fume hood is not handicap accessible. Eyewash is not handicap
accessible. There is no handicap accessible student worktable.
¨
219,
Science Lab: Fume hood is not handicap accessible. Eyewash is not handicap
accessible. There is no handicap accessible student worktable.
¨
Girls’
Locker Room bathrooms: There are no handicap accessible toilet, sink or
accessories. There is no accessible shower or changing booth.
¨
Stair
tower next to girls’ locker room: The handrails are not handicap compliant.
There is a moveable chair lift inside the stair tower.
¨
Boys’
Locker Room: The physical education teacher’s bathroom is not handicap
accessible. The locker room sinks, toilets and urinals are not handicap
accessible. There is no handicap accessible shower.
¨
Wood
Shop: Sink is not handicap accessible. Eyewash is not handicap accessible.
Bathroom at wood shop area does not have handicap toilet stall, sink, urinal or
accessories. Door is too narrow and has no side clearance.
¨
Corridor
drinking fountains are not handicap accessible.
¨
Boys’
Bathroom across from room 204: The entrance alcove is not handicap accessible.
There is no handicap accessible toilet stall, urinals, sinks or accessories.
¨
Girls’
Bathroom: Entrance is not handicap accessible. Door width, alcove door does not
have side clearance. There are no toilets, sinks or accessories that are
handicap compliant.
¨
Room
301: Eyewash is not handicap accessible. Teacher’s demonstration sink is not
handicap accessible. There is no student handicap station. The deluge shower is
not handicap accessible.
¨
Room
302: Eyewash is not handicap accessible. Teacher’s demonstration sink is not
handicap accessible. There is no student handicap station. The deluge shower is
not handicap accessible.
¨
Men’s
Bathroom on this floor: Toilets, urinal, sinks and accessories are not handicap
accessible. The entrance door is too narrow and does not have the side
clearance.
¨
Girls’
Bathroom: Toilets, toilet stalls, sinks and accessories are not handicap
accessible. The entrance door is too narrow and does not have the side
clearance.
¨
All
rooms in this wing do not have handicap accessible entrances because there is
no side clearance at the doors.
|
|